function ef = cpf_flim_event(cb_data, cx)
%CPF_FLIM_EVENT Event function to detect branch flow limit (MVA) violations
% EF = CPF_FLIM_EVENT(CB_DATA, CX)
%
% CPF event function to detect branch flow limit (MVA) violations,
% i.e. max(Sf,St) >= SrateA.
%
% Inputs:
% CB_DATA : struct of data for callback functions
% CX : struct containing info about current point (continuation soln)
%
% Outputs:
% EF : event function value
% MATPOWER
% Copyright (c) 2016-2017, Power Systems Engineering Research Center (PSERC)
% by Ray Zimmerman, PSERC Cornell
% and Ahmad Abubakar Sadiq, Federal University of Technology Minna, Nigeria
% and Shrirang Abhyankar, Argonne National Laboratory
%
% This file is part of MATPOWER.
% Covered by the 3-clause BSD License (see LICENSE file for details).
% See http://www.pserc.cornell.edu/matpower/ for more info.
%% event function value is nl x 1 vector equal to:
%% [ max(Sf,St) - SrateA ]
%% define named indices into bus, gen, branch matrices
[F_BUS, T_BUS, BR_R, BR_X, BR_B, RATE_A, RATE_B, RATE_C, ...
TAP, SHIFT, BR_STATUS, PF, QF, PT, QT, MU_SF, MU_ST, ...
ANGMIN, ANGMAX, MU_ANGMIN, MU_ANGMAX] = idx_brch;
%% get updated MPC
d = cb_data;
mpc = cpf_current_mpc(d.mpc_base, d.mpc_target, ...
d.Ybus, d.Yf, d.Yt, d.ref, d.pv, d.pq, cx.V, cx.lam, d.mpopt);
%% compute line flow MVA violations
SrateA = d.mpc_base.branch(:,RATE_A);
Sf = sqrt((mpc.branch(:, PF)).^2 + (mpc.branch(:, QF)).^2);
St = sqrt((mpc.branch(:, PT)).^2 + (mpc.branch(:, QT)).^2);
%% line flow event function
ef = max(Sf,St) - SrateA;