91 changes: 8 additions & 83 deletions lib/openstudio-standards/hvac_sizing/Siz.AirLoopHVAC.rb
Original file line number Diff line number Diff line change
Expand Up @@ -2,41 +2,17 @@
# Reopen the OpenStudio class to add methods to apply standards to this object
class OpenStudio::Model::AirLoopHVAC

# Sets all auto-sizeable fields to autosize
def autosize
self.autosizeDesignSupplyAirFlowRate
end

# Takes the values calculated by the EnergyPlus sizing routines
# and puts them into this object model in place of the autosized fields.
# Must have previously completed a run with sql output for this to work.
def applySizingValues

design_supply_air_flow_rate = self.autosizedDesignSupplyAirFlowRate
if design_supply_air_flow_rate.is_initialized
self.setDesignSupplyAirFlowRate(design_supply_air_flow_rate.get)
end

end

# returns the autosized design supply air flow rate as an optional double
def autosizedDesignSupplyAirFlowRate

return self.model.getAutosizedValue(self, 'Design Supply Air Flow Rate', 'm3/s')

end

# Retrieves an airloop sum of air terminal minimum heating flow rates: sum(Vpz_min)
def autosizeSumMinimumHeatingAirFlowRates
result = OpenStudio::OptionalDouble.new
name = self.name.get.upcase
sql = self.model.sqlFile
if sql.is_initialized
sql = sql.get
query = "SELECT Value
sql = sql.get
query = "SELECT Value
FROM tabulardatawithstrings
WHERE ReportName='ComponentSizingSummary'
AND ReportForString='Entire Facility'
WHERE ReportName='ComponentSizingSummary'
AND ReportForString='Entire Facility'
AND TableName='AirLoopHVAC'
AND ColumnName='Sum of Air Terminal Minimum Heating Flow Rates'
AND RowName='#{name}'
Expand All @@ -53,68 +29,17 @@ def autosizeSumMinimumHeatingAirFlowRates

end

# Retrieve an airloop's design outdoor air intake (Vot)
# Ideally, this would only be used to retrieve Vot when
# calculated by EnergyPlus' built-in design VRP calculations
def autosize621OutdoorAirIntakeFlow
flow_types = ['Heating', 'Cooling']
flow_rates = []
flow_types.each do |flow_type|
result = OpenStudio::OptionalDouble.new
name = self.name.get.upcase
sql = self.model.sqlFile
if sql.is_initialized
sql = sql.get
query = "SELECT Value
FROM tabulardatawithstrings
WHERE ReportName='Standard62.1Summary'
AND ReportForString='Entire Facility'
AND TableName='System Ventilation Requirements for #{flow_type}'
AND ColumnName='Outdoor Air Intake Flow Vot'
AND RowName='#{name}'
AND Units='m3/s'"
val = sql.execAndReturnFirstDouble(query)
if val.is_initialized
result = OpenStudio::OptionalDouble.new(val.get)
end
# Inconsistency in column name in EnergyPlus 9.0:
# "Outdoor Air Intake Flow - Vot" vs "Outdoor Air Intake Flow Vot"
# The following could be deleted if the inconsistency was ever fixed
if result.to_f == 0.0
query = "SELECT Value
FROM tabulardatawithstrings
WHERE ReportName='Standard62.1Summary'
AND ReportForString='Entire Facility'
AND TableName='System Ventilation Requirements for #{flow_type}'
AND ColumnName='Outdoor Air Intake Flow - Vot'
AND RowName='#{name}'
AND Units='m3/s'"
val = sql.execAndReturnFirstDouble(query)
if val.is_initialized
result = OpenStudio::OptionalDouble.new(val.get)
end
end
else
OpenStudio::logFree(OpenStudio::Error, 'openstudio.model.Model', 'Model has no sql file containing results, cannot lookup data.')
end
flow_rates << result.to_f
end

return flow_rates.max

end

# Retrieve an airloop's sum of air terminal maximum flow rates: sum(Vpz)
def autosizeSumAirTerminalMaxAirFlowRate
result = OpenStudio::OptionalDouble.new
name = self.name.get.upcase
sql = self.model.sqlFile
if sql.is_initialized
sql = sql.get
query = "SELECT Value
sql = sql.get
query = "SELECT Value
FROM tabulardatawithstrings
WHERE ReportName='ComponentSizingSummary'
AND ReportForString='Entire Facility'
WHERE ReportName='ComponentSizingSummary'
AND ReportForString='Entire Facility'
AND TableName='AirLoopHVAC'
AND ColumnName='Sum of Air Terminal Maximum Flow Rates'
AND RowName='#{name}'
Expand Down

This file was deleted.

This file was deleted.

Loading