M-Bus (Meter-Bus) is a European standard (EN 13757-2 physical and link layer, EN 13757-3 application layer) for the remote reading of gas or electricity meters. M-Bus is also usable for other types of consumption meters. The M-Bus interface is made for communication on two wires, making it very cost effective.
The library works, but it lacks proper documentation. Well, it lacks any kind of documentation to be honest.
The implementation is currently under heavy development. Its original intended use case was very specific, as a library to aid in the decoding of M-Bus telegrams sent over HTTP, and might thus not suite everyone.
Still, it is a generic library, and has been used is several different use cases.
- Decoding of re-encoded M-Bus frames sent from an Elvaco Wireless M-Bus master over HTTP.
- Communicating with M-Bus devices over RS-232 serial.
- Communication with M-Bus devices over RFC 2217.
- As a debugging tool to decode M-Bus frames.
Currently only the variable data structures are implemented. The library can only decode M-Bus frame. It does currently NOT support encoding and transmission of M-Bus frames, such as control frames.
However, if the need arises, missing pieces can be implemented on a request basis.
You can find a set of utilities in the tools
folder.
- mbus-serial-request-data.py
- mbus-serial-request-data-multi-reply.py
- mbus-serial-scan.py
- mbus-serial-scan-seconday.py
These tools can communicate over a serial device /dev/ttyX
or even over RFC2217 using the format rfc2217://host:port
.
If you are using ser2net
as a RFC2217 server. You need to configure it the following way:
2000:telnet:0:/dev/ttySX:2400 remctl banner
- Missing: Fixed data structure parsing.
- Missing: Encoding to M-Bus frames.
- Missing: Slave configuration.
- Missing: Extended VIF codes.
- Querying a M-Bus device over serial.
- Parsing of a complete telegram.
- Parsing of just the Used Data segment.
- Generation of a basic JSON structure from the telegram/user-data/records.
- data[str]: M-Bus frame data
Returns an object of either type WTelegramSndNr, TelegramACK, TelegramShort, TelegramControl or TelegramLong. If an error occurs, it will raise a MBusFrameDecodeError.
- state[bool]: set the global debug state
Produces debug messages to stdout.
- ser[pySerial connection]: an open pySerial object
- address: The target primary address
Sends a PING frame to address over the serial connection ser.
- ser[pySerial connection]: an open pySerial object
- length: The minimum length of the reply. An ACK frame is one (1) byte.
Reads an entire frame and returns the unparsed data.
- ser[pySerial connection]: an open pySerial object
- address: The target primary address
If req is None, build a new request frame using address and send it.
- ser[pySerial connection]: an open pySerial object
- secondary_address[str]: A target using secondary address format
Sends a select frame with the supplied secondary address.
More to come...
#!/usr/bin/python
import meterbus
data = "\x68\x6A\x6A\x68\x08\x01\x72\x43\x53\x93\x07\x65" \
"\x32\x10\x04\xCA\x00\x00\x00\x0C\x05\x14\x00\x00" \
"\x00\x0C\x13\x13\x20\x00\x00\x0B\x22\x01\x24\x03" \
"\x04\x6D\x12\x0B\xD3\x12\x32\x6C\x00\x00\x0C\x78" \
"\x43\x53\x93\x07\x06\xFD\x0C\xF2\x03\x01\x00\xF6" \
"\x01\x0D\xFD\x0B\x05\x31\x32\x4D\x46\x57\x01\xFD" \
"\x0E\x00\x4C\x05\x14\x00\x00\x00\x4C\x13\x13\x20" \
"\x00\x00\x42\x6C\xBF\x1C\x0F\x37\xFD\x17\x00\x00" \
"\x00\x00\x00\x00\x00\x00\x02\x7A\x25\x00\x02\x78" \
"\x25\x00\x3A\x16"
telegram = meterbus.load(data)
print telegram.records[3].parsed_value
~$ 2014-02-19T11:18
#!/usr/bin/python
import serial
import meterbus
address = 254
with serial.Serial('/dev/ttyACM0', 2400, 8, 'E', 1, 0.5) as ser:
meterbus.send_ping_frame(ser, address)
frame = meterbus.load(meterbus.recv_frame(ser, 1))
assert isinstance(frame, meterbus.TelegramACK)
meterbus.send_request_frame(ser, address)
frame = meterbus.load(meterbus.recv_frame(ser, meterbus.FRAME_DATA_LENGTH))
assert isinstance(frame, meterbus.TelegramLong)
print(frame.to_JSON())
Single Character | Short Frame | Control Frame | Long Frame |
---|---|---|---|
E5h | Start 10h | Start 68h | Start 68h |
C Field | L Field = 3 | L Field | |
A Field | L Field = 3 | L Field | |
Check Sum | Start 68h | Start 68h | |
Stop 16h | C Field | C Field | |
A Field | A Field | ||
CI Field | CI Field | ||
Check Sum | User Data (0-252 Byte) | ||
Stop 16h | Check Sum | ||
Stop 16h |
Please see the LICENSE file