Simulation of Industrial process unit on ESP32 board with ModbusTCP interface

License

Notifications You must be signed in to change notification settings

nielsolie/ICSUnitSim

 
 

Repository files navigation

ICSUnitSim on ESP32 board ("ICS on Chip")

Realtime Process Simulation of Plant Water Supply Unit

Simulation Generates logically correct Modbus signals of Water Supply facility using ESP32 MCU board with ModbusTCP interface

Simulation intended for HMI and DCS testing with realtime values and for ICS security research

Developed using Arduino IDE for ESP32 (ESP 32 MCU board is available on Aliexpress for approx price of 5$)

Version history

  • Added HMI project backup for output visualisation
  • V0.2 Introduced Pump AUTO functionality, adjustable setpoints, tank_drain variable on modbus
  • V0.1 Initial code with manual controls only

Table of Contents

HMI Visualisation Example

HMI_Project folder contains latest backup of Ignition HMI Project, restore it to you Ignition setup for below result.

HMI Demo

Current HMI Example is designed on Ignition SCADA by Inductive Automation

Free trial versions of HMI software like RapidSCADA, Ignition and Advantech is available on internet.

For simple Modbus values reading/writing you could use RMMS tool http://en.radzio.dxp.pl/modbus-master-simulator/

Simulation Setup

Connection diagram

Virtual process's P&ID

Simulation P&ID

Modbus addressing

!Important!: Modbus library uses 0 based adressing

  • Modbus Coils Offsets (read\write)
mot_start, address: 100, boolean, Start button, 1 to activate, returns to 0 after activation

mot_stop, address: 110, boolean, Stop button, 1 to activate, returns to 0 after activation

valve_state, address: 120, boolean 0-Closed 1-Open (Controlled by start/stop logic)

mat_auto, address:130, boolean, 1-Pump automatic mode(by setpoints), 0 - manual mode
  • Modbus input status (Discrete Inputs) Offsets(read only)
mot_run, address: 100, boolean, 1 running, 0 stop
mot_trip, address: 110, boolean, Motor trip state, cause: Tank full, Valve closed, Random trip (1 of 10000)
  • Modbus Input Register Offsets (read only)
mot_load, address: 100; Uint16, range:0-100, random motor load simulation

flowm_flow, address: 110, Uint16, range:0-10, flow value depending on mot_load 

tank_level, address: 120, Uint16, range:0-65000, 65000 value trips the motor, has constant (random of 4) drainage flow

tank_drain,  address: 130; Uint16, Random drain by process
  • Modbus Holding Register Offsets (read\write)
tank_Hi, address: 100; Uint16, adjustable Hi level setpoint, for turning motor OFF in AUTO mode

tank_Lo, address: 110; Uint16, adjustable Lo level setpoint, for turning motor ON in AUTO mode

Follow

Follow author on twitter for project updates https://twitter.com/supeyev/