AA55 protocol

tkubec edited this page Jun 25, 2021 · 4 revisions

Request format

Byte Value
0 0xAA
1 0x55
2 source (0xC0 by default)
3 target (0x7F by default)
4 control code
5 function code
6 length
7 - n data
(n+1) - (n+2) plain sum of all data bytes

E.g. :

 `0xAA 0x55 0xC0 0x7F 0x01 0x02 0x00 0x02 0x41`

Response

The response format is the same, but the source and target is swapped and the function code is incremented by 128.

If the response is not sent within 1 - 2 seconds, it was either lost (it happens in approx 1% cases) or the request was not recognized.

Known commands

The supported commands for various inverters are described elsewhere, e.g.: http://yamasun.com.tw/upload/F_20170313191367UrC8jo.PDF.

Probably all inverters support the inverter system info command, using control code 1 and function code 2.

The response for the system info request is:

Byte Value
0 - 4 version string
5 - 14 model string
15 - 30 manufacture or empty
31 - 46 serial number